Basic heat exchangers
|
 |
Function of the productBasic heat exchangers (hereafter referred to as heat exchangers) are designed as completing units for ?central air conditioners KTCZ with air capacity from 10,000 t? 25,000 m3/h.
Heat carrier is hot (superheated) water according to GOST 20955-75 at temperature not more than 180ºC and pressure not more than 1.2 MPa.
Diameter of supporting pipe should be indicated in the order.
Example: TBZ-10.10.01.16 UZ
TBZ - basic heat exchanger
10 - number of banks
10 - height
01 - version
16 - supporting pipe diameter
UZ - moderate climate, allocation category 3 |
Specification
Specification is detailed in Table.
Table
| Designation |
Heat-exchange
surface area, m2 |
Core are for
passage of air,
m2 |
Cross-section area
for passage of heat carrier, in pipes, m² |
Weight,
kg |
Overall
dimensions |
| d 16х1,5 |
d 22х1,5 |
d 16х1,5 |
d 22х1,5 |
d 16х1,5 |
d 22х1,5 |
d 16х1,5 |
d 22х1,5 |
| TBZ-10.10.01 UZ |
13,8 |
14,6 |
0,786 |
0,0008 |
0,00163 |
50 |
68 |
1000х997х180 |
| TBZ-10.10.02 UZ |
27,9 |
29,6 |
1,61 |
67 |
103 |
1827х997х180 |
| TBZ-10.12.01 UZ |
17,5 |
18,4 |
0,983 |
0,00066 |
0,00137 |
60 |
84 |
1000х1247х180 |
| TBZ-10.12.02 UZ |
35,2 |
37,3 |
2,014 |
82 |
128 |
1827х1247х180 |
| TBZ-10.15.02 UZ |
42,5 |
45,0 |
2,418 |
0,0008 |
0,00165 |
100 |
153 |
1827х1497х180 |
| TBZ-10.20.02 UZ |
57,1 |
60,4 |
3,225 |
0,0008 |
0,00166 |
126 |
202 |
1827х1997х180 |
| TBZ-15.10.01 UZ |
22,3 |
20,9 |
0,786 |
0,0012 |
0,00248 |
62 |
84 |
1000х997х180 |
| TBZ-15.10.02 UZ |
44,9 |
42,4 |
1,61 |
88 |
135 |
1827х997х180 |
| TBZ-15.12.01 UZ |
28,3 |
27,2 |
0,983 |
0,001 |
0,0021 |
74 |
107 |
1000х1247х180 |
| TBZ-15.12.02 UZ |
57,1 |
55,3 |
2,014 |
110 |
172 |
1827х1247х180 |
| TBZ-15.15.02 UZ |
69,2 |
65,5 |
2,418 |
0,0012 |
0,0025 |
132 |
204 |
1827х1497х180 |
| TBZ-15.20.02 UZ |
93,5 |
88,7 |
3,225 |
0,0012 |
0,00248 |
172 |
271 |
1827х1997х180 |
| TBZ-20.10.01 UZ |
27,1 |
29,1 |
0,786 |
0,00153 |
0,00326 |
67 |
103 |
1000х997х180 |
| TBZ-20.10.02 UZ |
54,6 |
59,2 |
1,61 |
101 |
172 |
1827х997х180 |
| TBZ-20.12.01 UZ |
34,3 |
36,8 |
0,983 |
0,0013 |
0,00274 |
82 |
128 |
1000х1247х180 |
| TBZ-20.12.02 UZ |
69,2 |
74,6 |
2,014 |
125 |
215 |
1827х1247х180 |
| TBZ-20.15.02 UZ |
83,8 |
90,0 |
2,418 |
0,00155 |
0,00331 |
151 |
258 |
1827х1497х180 |
| TBZ-20.20.02 UZ |
112,9 |
120,8 |
3,225 |
0,0016 |
0,00333 |
196 |
344 |
1827х1997х180 |
Design and operating principleHeat exchangers consist of heat-release elements, tube sheets, covers with pipe sockets to which flanges for inlet and outlet of heat carrier.
Heat exchangers are designed in 2 versions:
1 version - the heat release element is made of steel supporting pipe 16x1.5 mm and rolling aluminium finning with outer diameter 39 mm.
2 version - the heat release element is made of steel supporting pipe 22x1.5 mm and rolling aluminium finning with outer diameter 43 mm.
Heat exchangers are designed as multipass model. Heat carrier circulation sequence is set by partitions in the cover.
Connection to heat supply system is performed using flanges.
Heat-exchanging media motion pattern is cross-flow.
Guarantee period is 12 months.
|